Simple Self-Diagnosis by Malfunction Code For Daikin Indoor Unit
For error codes beginning with A or C, see table below.
For error codes beginning with 6, 7, 8 or 9, find causes here
For error codes beginning with U, find causes here
For error codes beginning with E, F, H, J, L, M or P, find causes here
Indoor Unit Error Codes and Contents | Supposed causes | Parts affected |
---|---|---|
A0 External protection device activated |
External protection device connected to the terminal strip T1-T2 of indoor unit is activated |
SkyAir, VRV, Package |
A1 Malfunction of indoor unit PCB |
Defective indoor unit PCB External factor (noise etc) |
RA, SkyAir, VRV, Heat reclaim ventilator, Chiller |
A3 Drain Level Control System Abnormality |
Drain clogging, upward slope, etc Defective drain pump Defective float switch or short circuit connector |
RA, SkyAir, VRV, Heat reclaim ventilator, Fan coil |
A4 Malfunction of freezing protection |
Shortage of water volume Low water temperature setting Defective water temperature thermistor |
RA, SkyAir, VRV, Package, Chiller, Fan coil |
A5 High pressure control in heating, freeze-up protection control in cooling |
Clogged air filter of indoor unit and short circuit Defect of indoor unit heat exchanger thermistor |
RA, SkyAir, VRV, Package |
A6 Malfunction of fan motor |
Broken wires in, short circuit of, or disconnection of connectors from the fan motor harness Defective fan motor Defective indoor unit PCB |
RA, SkyAir, VRV, Package, Heat reclaim ventilator |
A7 Malfunction of swing flap motor |
Defective swing flap motor Defective indoor unit PCB Defective connection cable Defective airflow direction adjusting flap-cam |
SkyAir, VRV |
A8 Malfunction of power supply or AC input overcurrent |
Defective power supply voltage Defective connection on signal line Defective wiring |
SkyAir, VRV, Heat reclaim ventilator |
A9 Malfunction of electronic expansion valve |
Defective electronic expansion valve coil Defective indoor unit PCB Defective relay cables |
SkyAir, VRV, Package, Heat reclaim ventilator. Chiller |
AA Heater overheat |
26WH is activated | Package, Chiller |
AF Malfunction of humidifier system |
Humidifier unit (optional accessory) leaking Defective drain piping (upward slope, etc.) Defective indoor unit PCB |
SkyAir, VRV, Heat reclaim ventilator |
AH Malfunction of dust collector of air cleaner |
Defect of dust collecting element Stained insulator part Defect of high voltage power supply unit Defect of indoor unit PCB |
RA, SkyAir, VRV, Fan coil |
AJ Malfunction of capacity setting (Indoor unit PCB) |
The capacity setting adaptor was not installed when replacing PCB Defective indoor unit PCB |
SkyAir, VRV, Package |
C1 Failure of transmission (between indoor unit PCB and sub PCB) |
Defective connection of the connector between indoor unit PCB |
SkyAir, VRV |
C4 Malfunction of liquid pipe thermistor for heat exchanger |
Defective thermistor for liquid pipe Defective indoor unit PCB Defective connector contact |
RA, SkyAir, VRV, Package, Heat reclaim ventilator, Chiller, Fan coil |
C5 Malfunction of gas pipe thermistor for heat exchanger |
Defective thermistor for gas pipe Defective indoor unit PCB Defective connector contact |
RA, VRV, Package, Heat reclaim ventilator, Chiller |
C6 Malfunction of fan motor sensor or fan control driver |
Defective fan PCB Defective connection of capacity setting adaptor Field setting error |
SkyAir, VRV |
C7 Front panel driving motor fault |
Defective front panel driving motor Defective limit switch |
RA |
C9 Malfunction of suction air thermistor |
Defective thermistor for suction air Defective indoor unit PCB Defective connector contact |
RA, SkyAir, VRV, Package, Heat reclaim ventilator, Fan coil |
CA Malfunction of discharge air thermistor |
Defective thermistor for discharge air Defective indoor unit PCB Defective connector contact |
RA, VRV, Package, Heat reclaim ventilator |
CC Malfunction of humidity sensor system |
Defective humidity sensor Defective connector contact |
RA, SkyAir, Package |
CJ Room temperature thermistor in remote controller abnormality |
Defective room temperature thermistor in remote controller Defective remote controller PCB External factor (Noise etc.) |
RA, SkyAir, VRV, Package, Fan coil |